The full DCX dry cooler range. Engineered to perform at +55°C ambient — the only realistic way to hit sub-1.2 PUE with warm-water cooling in the Gulf.
Capacity: 15 kW – 2 MW per unit. Every unit is DCX-engineered in Europe, certified for 45°C warm-water operation, and delivered with Middle East-grade corrosion protection. Backed by our Dubai and Doha-based engineering teams for design, installation and 24/7 service.
| Parameter | Value |
|---|---|
| Range | 15, 40, 120, 240, 1000, 2000 kW |
| Max ambient | +55°C (with adiabatic +60°C) |
| Water type | Treated water or glycol |
| Fan type | EC VFD low-noise |
| Adiabatic assist | Optional (water-saving pads) |
| Coil coating | Epoxy + aluminum fin standard |
| Noise level | 45–65 dB at 10m |
| Footprint | From 1.5 m² (15 kW) to 35 m² (2 MW) |
| Certifications | Eurovent, CE, ISO 9001 |
Compact footprint for urban sites
15-40 kW edge cabinets
120-240 kW mid-range
1-2 MW facility class
Matched to FDU 5/8 MW
Replace inefficient air-cooled chillers
Yes, with proper approach design. At 50°C ambient we size for 45°C water supply (a 5K approach). Adiabatic boost drops another 5-8°C during peaks.
Only during summer peaks (~200 hrs/year in Gulf). Typical consumption is 2–4 m³/hr — a fraction of cooling towers.
Our GCC-spec units ship with sand filters on fan inlets and epoxy-coated coils. Cleaning intervals are quarterly vs weekly for uncoated units.
Not directly — coil corrosion. We pair a seawater-to-freshwater plate heat exchanger upstream when coastal site water is available.
Our 2 MW unit is ~63 dB at 10m — well below most municipal limits.